Cd18 Software Revision Number

Cd18 displays the software revision number

Cd17 Relative Humidity (%)

Cd17 displays the humidity sensor (HS) reading, as a percent value.

Cd16 Compressor Motor / Unit Run Time Hour Meter

Unit Run Time Hour Meter

Cd16 displays the compressor motor hours. Press the ENTER key while in Cd16 to view unit run time. Total hours are recorded in increments of 10 hours (i.e., 3000 hours is displayed as 300).

Press and hold the ENTER key for 5 seconds to reset the Compressor Motor Hour Meter display. The Unit Run Time Hour Meter cannot be reset.

Cd15 Digital Unloader Valve / Digital Loader Valve

Cd15 displays the status of the digital unloader valve (DUV) as Open or Closed.

For PrimeLINE EDGE units (571-3xx models) the status of the digital loader valve (DLV) can also be displayed. To display the DLV status, press and hold the ENTER key for 3 seconds and continue to hold. When the key is released, the display switches back to the DUV.

Cd14 Compressor Discharge Pressure

Cd14 displays the compressor discharge pressure transducer (DPT) reading.

Cd12 Evaporator Pressure / Compressor Suction Pressure

Cd12 displays the evaporator pressure transducer (EPT) reading in the right display. Press the ENTER key to show the reading for the suction pressure transducer (SPT) in the left display and the EPT in the right display.

Cd11 Compressor Discharge Temperature

Cd11 displays the compressor discharge temperature Sensor (CPDS) reading, using compressor dome temperature.

Cd10 Evaporator Temperature

Cd09 displays the ambient temperature sensor (AMBS) reading.

Cd09 Ambient Temperature

Cd09 displays the ambient temperature sensor (AMBS) reading.

Cd08 Main Power Frequency

Cd08 displays the value of the main power frequency in Hertz. The frequency displayed will be halved if either fuse F1 or F2 is bad (alarm code AL021).

Cd07 Main Power Voltage

Cd07 displays the main supply voltage.

Cd04 Cd05 Cd06 Line Current Phase A B C

These codes display the measured of Phase A (Cd04), B (Cd05) and C (Cd06) in amperes. The current sensor measures current on two legs. The third unmeasured leg is calculated based on a current algorithm. The current measured is used for control and diagnostic purposes.

For control processing, the highest of the Phase A and B current values is used for current limiting purposes. For diagnostic processing, the current draws are used to monitor component energization.

Whenever a heater or a motor is turned ON or OFF, the current draw increase/reduction for that activity is measured. The current draw is then tested to determine if it falls within the expected range of values for the component.

Failure of this test will result in a pre-trip failure or a control alarm indication.

Cd03 Compressor Motor Current

Cd03 displays the current value passing through the compressor motor leg T3. The current sensor measures current draw in lines L1 & L2 by all of the high voltage components. It also measures current draw in compressor motor leg T3.

Cd01 Capacity Modulation (%)

Cd01 displays the DUV percent closed. The right display reads 100% when the valve is fully closed. The valve will usually be at 10% on start up of the unit except in very high ambient temperatures.

Tuesday, October 14, 2025

Thermo King MP4000 transformer

Be careful before replace compressor contactor - Checks voltage on the terminal 7 8 must in range 24v to 29v. 
If volt over from the range contactor still can operated as a normal but overheat

Monday, October 13, 2025

TechFact: PrimeLINE® Unit P6-5 Test

In conjunction with our December 2013 TechLINE article (pre-trip P6-5), Carrier Transicold has introduced the following procedures to assist the technician in troubleshooting a P6-5 occurrence.  

PrimeLINE® unit pre-trip P6-5 ensures that the compressor holds pressure internally, assuming the ESV (P6-6), DUV (P6-7) and EEV (P6-10) are working correctly. Due to the complexity of P6-5 testing, the best practice is to always use the latest version of software to ensure that the most up to date diagnostic is used. 

At the start of pre-trip P6-5, the compressor will run to create a pressure differential between the suction and discharge of the compressor.  On completion, the compressor is turned off. If the suction side pressure does not increase more than 8 psi, the test passes, otherwise, the test fails. If the test fails, the cause of the leakage needs to be determined.

The 8 psi rise in suction pressure may be attributed to high pressure returning back to the compressor through a leak at any of the following refrigeration circuits:

# Electronic Expansion Valve (EEV)
# Economizer Expansion Valve (ESV)
# Digital Unloader Valve (DUV)
# Pressure Transducer (DPT, SPT, EPT)
# Compressor

The following procedures are recommended to assist the technician in the troubleshooting
procedure.

1. Confirm software Rev.
a. Access Cd18.
b. Confirm software is revision is 5365 (or greater). Seek agreement from the equipment owners if necessary, otherwise, update software to latest version and run P6-5.

2. Test Pressure Transducers (DPT, SPT, EPT)
a. Remove DPT, SPT and EPT from the refrigeration system.
b. Check Cd14 and Cd12 - Cd12 will display suction pressure in the right display. Pressing ENTER again will display evaporator pressure in the left window.
c. At sea level the disconnected DPT, SPT and EPT should all read zero. Above Sea level all the transducers should be reading the same. Replace defective Pressure Transducers, if necessary.

3. Run Pre-trip P7
a. Press PRE-TRIP, use the arrow key to scroll to test P7, then press “ENTER”.
b. The controller will initiate the High Pressure Test. If the compressor internal seals are leaking, it will fail P7.
 
4. Test EEV
a. Connect Manifold Gauge Set (MGS) to discharge (DSV) and suction (SSV) service valves, and midseat them.
b. Access Cd41.
c. Press “ENTER” key to select tIM, and set to 5 min, using the arrow keys.
d. Press “ENTER” key twice to select EEV and set to “0” using the arrow keys, then press “ENTER.”
e. Allow suction pressure to pull down to a vacuum, as shown on MGS. Troubleshoot and replace defective EEV (valve and or coil) if necessary.
f. Perform a power cycle to reset Cd41 setting, retest EEV if necessary.

5. Test DUV
a. Front seat the Liquid Line Service Valve and pump down the refrigerant. To perform an Automatic Pump Down using Cd59 Pump down Logic, refer to Service and Operations Manual T362 for more info.
b. Front seat the discharge and suction service valves to isolate the compressor.
c. Disconnect DUV from the top of compressor.
d. Install a ½ to ¼ inch flared adapter / O-ring (CTD# 40- 50076-00SV) to the DUV side.
e. Pressurize the line to 50 psi (3.5 bar) of nitrogen at the adapter connection, then close supply at the tank.
f. If pressure decreases at the tank regulator; the DUV is leaking and should be replaced.
g. If DUV is not leaking, energize DUV by removing coil and placing a magnet on the valve stem. This should open the valve. If the pressure does not decrease at the tank regulator, replace the valve as it did not open
6. Test ESV
a. If the DUV passes, remove the flare adapter / O-ring (CTD# 40-50076- 00SV) from the DUV side, and reconnect the line to the top of the compressor.
b. Disconnect the economizer line from the compressor.
c. Connect a tank of dry nitrogen to the Liquid Line Service valve (it should already be front seated during the pump down procedure) and pressurize the system to 50 psig, then close the supply at the tank.
d. If pressure decreases at the tank regulator, and nitrogen can be detected coming out of the economizer line; the ESV is leaking and should be replaced.
e. If ESV is not leaking, energize ESV by removing coil and placing a magnet on the valve stem. This should open the valve. If the pressure does not decrease at the tank regulator or you cannot feel or hear the nitrogen escaping through the disconnected economizer line, replace the ESV as it did not open.

Following these steps in checking the Software, Pressure Transducers, EEV, DUV and ESV ensures all are working properly leaving the compressor as the root cause of the failure. Following is a quick
P6-5 checklist for trouble shooting.
# Ensure software is revision 5365 (or greater); if not, update software to latest version and
re-run P6-5.
# Disconnect the DPT, SPT and EPT and verify pressures. Replace defective Pressure Transducers if necessary.
# Perform P7 and make sure it passes P7 test.
# Perform EEV Test via Cd41, confirm suction pressure to pull down to a vacuum as shown on MGS (Micron gauge).
# Perform DUV Test, confirm DUV is not leaking, valve opening and closing.
# Perform ESV Test, confirm ESV is not leaking, valve opening and closing.
# Ensure system pressures are correct post testing when using nitrogen for leak tests. If you have any questions, contact your Regional Service Engineer, together with a Controller Download (all data).