04 Evaporator Coil Sensor Open Circuit (Check Alarm)

Thermo King Alarm Code
Description Corrective Action
Evaporator Coil Sensor Open Circuit (Check Alarm
  • Sensor circuit resistance higher than 100,000 ohms.
  • Temperature below -70C (-94F).
  • Indicates:
  • Open circuit to sensor
  • Defective or wrong sensor
  • Defective relay board
  • Defective cable No.1
  • Defective controller
  • Low evaporator coil temperature
  • Check sensor resistance between pins 5 and 6 on plug J15. Resistance must be 2,000 ohms at 25C (77F).
  • Check cable No.1 between controller and rela board.
  • Check evaporator air flow.