06 Compressor Current Too High MP4000
Description
Compressor Current Too High
- Occurs during pretrip (PTI) or function test only.
- During compressor test, if Compressor power
consumption is 25% above expected current draw
or compressor phase current level differs 33% or
more.
- If both alarm #6 and #7 is active this indicates too
high phase difference.
- Expected compressor current is a function of the
surrounding conditions.
- Indicates:
- Defective Digital Control valve.
- Defective compressor.
- Defective volt or amp meter on power module.
- Inaccurate ambient, condenser or evaporator
temperature measurement.
- Excessive condenser pressure due to air or
wrong refrigerant in system, or refrigerant over
charge
Corrective Action
- Check evaporator and condenser sensor
temperatures for correct value (± 5 C [± 9 F])
by viewing Data menu.
- To determine the current draw measurement,
enter Manual Function Test menu. Start and
check current draw of the following
components separately and together:
compressor, compressor full loaded,
condenser fan and evaporator fan (high or
low).
- Check power supply volts on all 3 phases.