06 R-134 Compressor Current Too High (Check Alarm)

Thermo King Alarm Code
Description Corrective Action
Compressor Current Too High (Check Alarm
  • Occurs during Pretrip (PTI) or Function test only.
  • Compressor power consumption is 25% above expected current draw (above approximately 13 amps); or compressor phase current level difference of 10% or more, depending on ambient temperature.
  • Indicates:
  • (Defective KVQ valve if CRR Model) (Defective stepper valve if CSR Model)
  • Defective compressor or valve plate
  • Defective volt or amp meter on relay board
  • Inaccurate ambient, condenser or evaporator temperature measurement
  • Out of range power supply
  • Excessive condenser pressure due to air or wrong refrigerant in system, or refrigerant over charge
  • Check evaporator, condenser and ambient sensor temperatures for correct value (+/- 5 C [+/- 9 F]) by viewing Data menu.
  • Enter Manual Function Test menu. Start and check current draw of the following components separately and together: compressor, compressor 100%, condenser fan and evaporator fan (high and low).
  • Check volt and ampere meter.
  • Check power supply volts.