Compressor Current Too High (Check Alarm
- Occurs during Pretrip (PTI) or Function test only.
- Compressor power consumption is 25% above expected current draw (above approximately 13 amps); or compressor phase current level difference of 10% or more, depending on ambient temperature.
- Indicates:
- (Defective KVQ valve if CRR Model) (Defective stepper valve if CSR Model)
- Defective compressor or valve plate
- Defective volt or amp meter on relay board
- Inaccurate ambient, condenser or evaporator temperature measurement
- Out of range power supply
- Excessive condenser pressure due to air or wrong refrigerant in system, or refrigerant over charge
|
- Check evaporator, condenser and ambient sensor temperatures for correct value (+/- 5 C [+/- 9 F]) by viewing Data menu.
- Enter Manual Function Test menu. Start and check current draw of the following components separately and together: compressor, compressor 100%, condenser fan and evaporator fan (high and low).
- Check volt and ampere meter.
- Check power supply volts.
|