105 | Tsup 1 invalid |
---|---|
Description | Supply Air Temperature Sensor 1 Invalid |
Cause | Indication of defective supply air temperature sensor, its measuring circuitry or sensor not mounted correctly in unit |
Trouble shooting |
Possible causes:
Trouble shooting:
a) If the resistance is out of range, see “30.2 Temperature Sensor [°C] - Resistance Table” p. 185, the temperature sensor and cable are defective and should be replaced. b) If the resistance is within range, perform main controller check “16.1 Trouble shooting for Star Cool main controller” p. 60 before replacing main controller. |
Criteria | Value is below alarm limit -60°C (-76°F) or above +140°C (284°F) or difference between Tsup1 and Tsup2 is more than (>) 1°C (1,8°F) for 30 min. Value invalid for 30 sec. for alarm activation. |
105 StarCool Alarm Codes And Actions