Probe Error (Check Alarm)
- Occurs during Pretrip (PTI) test or Probe Test failed in CHilled mode
- Temperature difference between return air and supply air sensors is too high (0.8 C[1.5 F]
|
- Check sensor connections. Check sensor resistance of each sensor. Resistance must be 2,000 ohms at 25 C (77 F).
- Check left hand and right hand supply air sensor locations.
|