119 Digital Valve Error MP4000
Description
Digital Valve Error
- Occurs during pretrip (PTI) test only.
- Compressor Current consumption not correct for
valve position.
Corrective Action
- Using Manual Function Test, without
compressor and fans active check the function
of the valve by observing the sound or feel of
the valve while activating/deactivating.
- Using Manual Function Test, with compressor
and fans active check the function of the
valve.
- The current consumption during NOT
energized valve must be higher than during
energized position.
- With Condenser coil temperature above
35C the expected increase is min 0,9A and
below 35C expected limit is 1,5A.