120 Suction Pressure Sensor Error MP4000
Description
Suction Pressure Sensor Error
- Occurs during Normal Run if the sensor is detected
to be out of range, open or short circuit.
- Occurs during pretrip (PTI) test if the sensor
readings do not act correct during compressor
activity.
- Expected to decrease 0,15Bar from stopped to
compressor running loaded.
- Indicates:
- Wrong location of the sensor.
- Sensor failure.
Corrective Action
- Using DATA menu evaluate sensor readings.
- Check wiring to be correct and connected.
- Check J1 plug is plugged into MRB.
- Check voltage at J1 pin7 to be 0.5 – 4.5 volts.
- Replace sensor.