123 | Tevap invalid |
---|---|
Description | Evaporator Temperature Sensor Invalid |
Cause | Indication of defective evaporator temperature sensor or its measuring circuitry |
Trouble shooting |
Possible causes:
Trouble shooting:
a) If the resistance is out of range, see “30.2 Temperature Sensor [°C] - Resistance Table” p. 185, the temperature sensor and cable are defective and should be replaced. b) If the resistance is within range, perform main controller check “16.1 Trouble shooting for Star Cool main controller” p. 60 before replacing main controller. |
Criteria | Value below alarm limit -60°C (-76°F) or above +140°C (+284°F). Value must be invalid for 30 sec. for alarm activation. |