126 | Tsuc invalid |
---|---|
Description | Suction Temperature Sensor Invalid |
Cause | Indication of defective suction temperature sensor or its measuring circuitry |
Trouble shooting |
Possible causes:
Trouble shooting:
a) If the resistance is out of range, see “30.2 Temperature Sensor [°C] - Resistance Table” p. 185, the temperature sensor and cable are defective and should be replaced. b) If the resistance is within range, perform main controller check “30.2 Temperature Sensor [°C] - Resistance Table” p. 185 before replacing main controller. |
Criteria | Value below alarm limit -60°C (-76°F) or above +140°C (+284°F). Value must be invalid for 30 sec. for alarm activation. |