127 Alarm General Unit Error MP4000

Description 

Alarm General Unit Error 

  • The surveillance has determined that the unit is not capable of continue running, and has shut down. 
  • The reason is displayed at the controller main screen, and is stated at the event next to the alarm event. 
  • Known reason to the shutdown state is: 
    • “SET POINT OUT OF RANGE” 
    • “VOLTAGE OUT OF RANGE” 
    • “POWER LINE PHASE ERROR” 
    • “REGULATION PROBE ERROR” 
    • “COMPRESSOR TEMPERATURE HIGH” 

Corrective Action 

“SET POINT OUT OF RANGE” 
  • The temperature set point is outside valid operation range. +30°C to -40°C (+35°C with extended range). 
  • Check configurations and settings on the controller. 
“VOLTAGE OUT OF RANGE” 
  • The measured voltage is below 330VAC. 
  • Check power line voltage while loaded. 
“POWER LINE PHASE ERROR” 
  • The phase detection system detects phase error or not capable of securing the correct rotation. 
  • Check power line voltage and quality. 
“REGULATION PROBE ERROR” 
  • If supply and return air temperature sensor and evaporator coil temperature sensors ALL indicate OPEN or SHORT circuit, the software is not capable of determine a reasonable action related to the cargo. 
  • Follow steps related to the sensor alarms. 
“COMPRESSOR TEMPERATURE HIGH” 
  • The compressor temperature is measured to be above 148°C. The state will stay until compressor temperature is measured to be below 132°C. 
  • Check refrigerant level and flow through the cooling circuit.