127 Alarm General Unit Error MP4000
Description
Alarm General Unit Error
- The surveillance has determined that the unit is not
capable of continue running, and has shut down.
- The reason is displayed at the controller main
screen, and is stated at the event next to the alarm
event.
- Known reason to the shutdown state is:
- “SET POINT OUT OF RANGE”
- “VOLTAGE OUT OF RANGE”
- “POWER LINE PHASE ERROR”
- “REGULATION PROBE ERROR”
- “COMPRESSOR TEMPERATURE HIGH”
Corrective Action
“SET POINT OUT OF RANGE”
- The temperature set point is outside valid
operation range. +30°C to -40°C (+35°C with
extended range).
- Check configurations and settings on the
controller.
“VOLTAGE OUT OF RANGE”
- The measured voltage is below 330VAC.
- Check power line voltage while loaded.
“POWER LINE PHASE ERROR”
- The phase detection system detects phase
error or not capable of securing the correct
rotation.
- Check power line voltage and quality.
“REGULATION PROBE ERROR”
- If supply and return air temperature sensor
and evaporator coil temperature sensors ALL
indicate OPEN or SHORT circuit, the software
is not capable of determine a reasonable
action related to the cargo.
- Follow steps related to the sensor alarms.
“COMPRESSOR TEMPERATURE HIGH”
- The compressor temperature is measured to
be above 148°C. The state will stay until
compressor temperature is measured to be
below 132°C.
- Check refrigerant level and flow through the
cooling circuit.