128 Supply Air Temperature Probe Error MP4000
Description
Supply Air Temperature Probe Error
- Occurs during pretrip (PTI) test and probe test only.
- After ventilation with the evaporator fans.
- If the supply and return air temperature sensor
differs more than 1,5C and the return air
temperature is within 1,5C of evaporator coil
temperature.
- If evaporator coil temperature sensor is failing, if the
supply and return air temperature sensors differs
more than 1,5C. Both alarm 129 and 128 will be set.
- Indicates:
- Failing sensors.
- Misplaced sensors.
- Failing controller.
Corrective Action
- Use the DATA menu to detect the failing
sensor.
- Replace sensors.
- Use the tester to determine the problem.