Alarm Code #411
Model CPE52, 53, 14, 15, 15V, 16
Failure Lock or short circuit of Compressor
Motor ( CM or CML )
Countermeasure
<<
Cause -(1) >>
(1)
Compressor start failure due to too low power supply voltage
(2)
Compressor start failure due to overload
<
Check > ( Refer to Page F-29 )
After
leaving the Reefer Unit as it stops for one hour, operate again the unit
and
check the compressor running current with a clamp meter.
<
Action >
In
case the compressor current is the following current value, replace the
compressor.
•
CPE52, 53, 15 : AC 15A or over ( at 440V )
• CPE14, 15V, 16 : AC
25A or over ( at 440V )