Mitsubishi Alarm Code #411 cause 1



Alarm Code #411
Model CPE52, 53, 14, 15, 15V, 16
Failure Lock or short circuit of Compressor Motor ( CM or CML )
Countermeasure
<< Cause -(1) >>
(1) Compressor start failure due to too low power supply voltage
(2) Compressor start failure due to overload
< Check > ( Refer to Page F-29 )
After leaving the Reefer Unit as it stops for one hour, operate again the unit
and check the compressor running current with a clamp meter.
< Action >
In case the compressor current is the following current value, replace the compressor.
• CPE52, 53, 15 : AC 15A or over ( at 440V )
• CPE14, 15V, 16 : AC 25A or over ( at 440V )