Alarm Code #415
Model CPE15 ( Only Two Compressor Type )
Failure Lock or Shot circuit of Compressor
Motor ( CMR )
Countermeasure
<<
Cause -(1) >>
(1)
Compressor start failure due to too low power supply voltage
(2)
Compressor start failure due to overload
<
Check > ( Refer to Page F-30 )
After
leaving the Reefer Unit as it stops for one hour, operate again the unit and
check the compressor running current with a clamp meter.
<
Action >
In
case the compressor current is AC 15A or over ( at AC 440V ), replace the compressor.