13 Evaporator Fan High Speed Current Too Low

Thermo King Alarm Code
Description Corrective Action
Evaporator Fan high Speed Current Too Low (Check Alarm)
  • Occurs during Pretrip (PTI), Function test or Probe test. 
  • (Evaporator fan power consumption is 25% below expected current draw (below 1.5 to 2.3 amps, depending on voltage). If CRR Model)
  • (Evaporator fan power consumption is 25% below expected current draw (below 1.6 to 2.4 amps, depending on voltage). If CSR Model)
  • Indicates:
  • Defective evaporator fan motor relay
  • Defective or open fan motor internal over temperature protection switch
  • Defective volt or amp meter on relay board
  • Incorrect motor or motor connections
  • Open evaporator door and make sure all fans rotate freely.
  • Enter manual Function Test and start evaporator fans on HIGH speed. Make sure all fans start on high speed. If a motor does not start and is very hot, wait 10 minutes for internal over temperature switch to close.
  • Check fan motor volts and amps
  • Check volt and ampere meter.