13 Evaporator Fan High Speed Current Too Low MP4000
Description
Evaporator Fan High Speed Current Too Low
- Occurs during pretrip (PTI) or function test only.
- Fan power consumption is 33% below expected
current draw or phase current level differs 33% or
more.
- If both alarm #12 and #13 is active this indicates
too high phase difference.
- Expected fan current is a function of the power line
frequency and the supply voltage.
- With 20’ setting below approximately
- - 1,4Amp@400VAC/50Hz
- - 2,0Amp@460VAC/60Hz
- With 40’ setting below approximately
- - 0,9Amp@400VAC/50Hz
- - 1,4Amp@460VAC/60Hz
- Indicates:
- Defective or open fan motor internal over
temperature protection switch.
- Incorrect motor or motor connections.
- Defective volt or amp meter on power module.
Corrective Action
- Open evaporator door and make sure all fans
rotate freely.
- Enter Manual Function Test and start
evaporator fans on high speed. Make sure all
fans start on high speed. If a motor does not
start and is very hot, wait 10 minutes for
internal over temperature switch to close.
- Enter Manual Function Test and start
evaporator fans on high speed. Make sure all
fans start on high speed. Check fan motor
volts and amps.
- With 20’ setting expect
- - 2,4Amp@400VAC/50Hz
- - 3,1Amp@460VAC/60Hz
- With 40’ setting expect
- - 1,8Amp@400VAC/50Hz
- - 2,4Amp@460VAC/60Hz
No comments :
Post a Comment