137 Sensor System Overload MP4000
Description
Sensor System Overload
- The controller sensor measurement is overloaded.
- This situation will probably introduce wrong
readings at other sensors than the one introducing
the overload.
- Indicates:
- Not intended voltage is introduced at one of the
sensor inputs.
- Transducer, connection or cabling with voltage
supply for the sensor might short circuit this
voltage supply onto the measuring input.
Corrective Action
- Sensor input which might initiate the problem:
- At connector J3:
- Humidity sensor (4-20mA type) pin 15-16.
- At connector J1:
- AVL position pin 1-3.
- Discharge pressure pin 4-6.
- Suction pressure pin 7-9.
- At least one of the sensors circuits holds a
short between sensor voltage and sensor
signal.
- Problem might be located any were from the
connection to the sensor itself.
- Action:
- Disconnect sensors and look for a non
intended short between sensor voltage and
the sensor line.
- The sensor with the problem might show up
with its own alarm.