137 Sensor System Overload MP4000

Description 

Sensor System Overload 

  • The controller sensor measurement is overloaded. 
  • This situation will probably introduce wrong readings at other sensors than the one introducing the overload. 
  • Indicates: 
  • Not intended voltage is introduced at one of the sensor inputs. 
  • Transducer, connection or cabling with voltage supply for the sensor might short circuit this voltage supply onto the measuring input. 

Corrective Action 

  • Sensor input which might initiate the problem: 
    • At connector J3: 
      • Humidity sensor (4-20mA type) pin 15-16. 
  • At connector J1: 
    • AVL position pin 1-3. 
    • Discharge pressure pin 4-6. 
    • Suction pressure pin 7-9. 
  • At least one of the sensors circuits holds a short between sensor voltage and sensor signal. 
  • Problem might be located any were from the connection to the sensor itself. 
  • Action: 
    • Disconnect sensors and look for a non intended short between sensor voltage and the sensor line. 
    • The sensor with the problem might show up with its own alarm.