14 Evaporator Fan Low Speed Current Too High (Check Alarm)

Thermo King Alarm Code
Description Corrective Action
Evaporator Fan Low Speed Current Too High (Check Alarm)
  • Occurs during Pretrip (PTI) or Function test only.
  • (Evaporator fan power consumption is 25% above expected current draw (above 2.8 to 4.0 amps, depending on voltage).If CRR Model)
  • (Evaporator fan power consumption is 25% above expected current draw (above 1.0 to 2.0 amps, depending on voltage).If CSR Model)
  • Indicates:
  • Defective or stuck evaporator fan motor
  • Incorrect motor or motor connections
  • Motor high and low speed connection are interchanged
  • Defective volt or amp meter on relay board
  • Open evaporator door and make sure all fans rotate freely.
  • Enter Manual Function Test and start evaporator fans on LOW speed. Make sure all fans start on low speed. Check fan motor volts and amps.
  • Check volt and ampere meter.