Evaporator Fan Low Speed Current Too High (Check Alarm)
- Occurs during Pretrip (PTI) or Function test only.
- (Evaporator fan power consumption is 25% above expected current draw (above 2.8 to 4.0 amps, depending on voltage).If CRR Model)
- (Evaporator fan power consumption is 25% above expected current draw (above 1.0 to 2.0 amps, depending on voltage).If CSR Model)
- Indicates:
- Defective or stuck evaporator fan motor
- Incorrect motor or motor connections
- Motor high and low speed connection are interchanged
- Defective volt or amp meter on relay board
|
- Open evaporator door and make sure all fans rotate freely.
- Enter Manual Function Test and start evaporator fans on LOW speed. Make sure all fans start on low speed. Check fan motor volts and amps.
- Check volt and ampere meter.
|