Trouble
shooting |
Possible causes:
- Discrepancy between calculated compressor and expansion valve mass flow of more than 25%
Trouble shooting:
- Check datalog alarm parameter 3
- Parameter 3: 1 – 3
- Check pressure transmitter Psuc and Pdis respectively
- Check wires to pressure transmitters for cuts, bends etc.
- If AL9XX voltage reference Psuc/Pdis are active, check controller.
- Check schraeder valve or remove schraeder insert and place decal
- Parameter 3: 4 - 6
- If parameter 3 is set to 4, Unit is running FC emergency -> Replace the FC.
- If parameter 3 is set to 5, perform pump down to confirm valve leakage inside compressor. -> replace valve plates. Check that the expansion valve is not blocked and that it is able to open.
- Check schraeder valve on Psuc -> replace/remove
- If parameter 3 is set to 6, check refrigerant level -> top up or recharge
- Run compressor & valve test to confirm blockage/function on Vexp ->
- If Vexp is not opening, check valve with permanent magnet
- Check coil, wire or controller -> AL9xx voltage reference?
|