Evaporator Fan Low Speed Current Too Low (Check Alarm)
- Occurs during Pretrip (PTI) or Function test only.
- Evaporator fan power consumption is 25% below expected current draw (below 0.6 to 1.2 amps, depending on voltage).
- Indicates:
- Defective evaporator fan motor relay
- Defective or open fan motor internal over temperature protection switch
- Defective volt or amp meter on relay board
- Incorrect motor or motor connections
|
- Open evaporator door and make sure all fans rotate freely.
- Enter Manual Function Test and start evaporator fans on LOW speed. Make sure all fans start on low speed. if a motor does not start and is very hot, wait 10 minutes for internal over temperature switch to close.
- Check fan motor volts and amps
- Check volt and ampere meter.
|