16 Condenser Fan Current Too High (Check Alarm)

Thermo King Alarm Code
Description Corrective Action
Condenser Fan Current Too High (Check Alarm)
  • Occurs during Pretrip (PTI) or Function test only.
  • Condenser fan power consumption is 25% above expected current draw (above 1.5 to 1.9 amps, depending on voltage).
  • Indicates:
  • Defective or stuck condenser fan motor
  • Defective volt or amp meter on relay board
  • Incorrect motor or motor connections
  • Enter Manual Function Test and start condenser fan. make sure the fan starts. Check fan motor volts and amps.
  • Check power supply volts and amps.
  • Check volts and ampere meter.