16 Condenser Fan Current Too High MP4000
Description
Condenser Fan Current Too High
- Occurs during pretrip (PTI) or function test only.
- Fan power consumption is 33% above expected
current draw or phase current level differs 33% or
more.
- If both alarm #16 and #17 is active this indicates
too high phase difference.
- Expected fan current is a function of the power line
frequency and the supply voltage.
- Above approximately
- - 1,5Amp@400VAC/50Hz
- - 1,8Amp@460VAC/60Hz
- Indicates:
- Defective or stuck condenser fan motor.
- Incorrect motor or motor connections.
- Defective volt or amp meter on power module.
Corrective Action
- Enter Manual Function Test and start
condenser fan. Make sure the fan starts.
- Check fan motor volts and amps.
- Expect
- - 1,0Amp@400VAC/50Hz
- - 1,2Amp@460VAC/60Hz