Temperature Too Far from Setpoint (Check Alarm)
- After 75 minutes of operation, supply or return air temperature is not in-range and does not approach setpoint within preset pulldown rate.
- Indicates:
- Ice or frost on evaporator coil
- Low refrigerant charge
- Air exchange vent open too much
- Container air leakage (doors open)
|
- Press SUP/RET key to check supply and return air sensor temperatures. COmpare temperatures to evaluate unit cooling capacity and performance.Temperature difference should be 4 C to 6 C.
- Open evaporator door. Inspect coil for rice or frost and initiate manual defrost if necessary.
- Check refrigerant charge
NOTE: This alarm can be activated if the supply or return air temperature varies, even if the mean temperature does approach setpoint. |