19 Temperature Too Far from Setpoint (Check Alarm)

Thermo King Alarm Code
Description Corrective Action
Temperature Too Far from Setpoint (Check Alarm)
  • After 75 minutes of operation, supply or return air temperature is not in-range and does not approach setpoint within preset pulldown rate.
  • Indicates:
  • Ice or frost on evaporator coil
  • Low refrigerant charge
  • Air exchange vent open too much
  • Container air leakage (doors open)
  • Press SUP/RET key to check supply and return air sensor temperatures. COmpare temperatures to evaluate unit cooling capacity and performance.Temperature difference should be 4 C to 6 C.
  • Open evaporator door. Inspect coil for rice or frost and initiate manual defrost if necessary.
  • Check refrigerant charge
 NOTE: This alarm can be activated if the supply or return air temperature varies, even if the mean temperature does approach setpoint.