19 Temperature Too Far From Setpoint MP4000
Description
Temperature Too Far From Setpoint
- Occurs during Normal Run only.
- After 75 minutes of operation, supply or return air
temperature is not in-range and does not approach
setpoint within preset pull-down rate.
- Indicates:
- Ice or frost on evaporator coil.
- Low refrigerant charge.
- Air exchange vent open too much.
- Container air leakage (doors open).
Corrective Action
- Use DATA menu to check supply and return
air sensor temperatures.
- Compare temperatures to evaluate unit
cooling capacity and performance.
- Temperature difference should be 4 C to 6 C
(7.2 F to 10.8 F).
- Open evaporator door. Inspect coil for ice or
frost and initiate manual defrost if necessary.
• Check refrigerant charge
NOTE: This alarm can be activated if the
supply or return air temperature varies,
even if the mean temperature does
approach setpoint.