20 Defrost Time Too Long (Check Alarm)

Thermo King Alarm Code
Description Corrective Action
Defrost Time Too Long (Check Alarm)
  • Heat signal has been ON for more than 90 minutes on 60 Hz power during Defrost (120 minutes on 50 Hz power).
  • Indicates:
  • Low power supply voltage
  • Defective heater elements
  • Defective evaporator high temperature protection switch Defective heat relay
  • Evaporator fans running during defrost
  • Evaporator sensor placed wrong
  • Initiate a manual defrost and check amperage draw and evaporator coil temperature. Evaluate defrost performance.
  • Open evaporator door and check location of evaporator coil sensor.
NOTE: This alarm can be activated at low voltage and very low box temperature conditions, even under normal operating conditions.