20 Defrost Time Too Long MP4000

Description

Defrost Time Too Long 

  • May occur during any defrost. 
  • Heat signal has been on for too long. 
  • Time limit is 90 minutes with supply voltage above 440VAC and 120 minutes below 440VAC. 
  • Indicates: 
  • Low power supply voltage. 
  • Defective heater elements. 
  • Evaporator fans running during defrost. 
  • Evaporator sensor placed wrong. 

Corrective Action 

  • Initiate a manual defrost and check amperage draw and evaporator coil temperature. Evaluate defrost performance. 
  • Open evaporator door and check location of evaporator coil sensor. 
NOTE: This alarm can be activated at low voltage and very low box temperature conditions, even under normal operating conditions.