20 Defrost Time Too Long MP4000
Description
Defrost Time Too Long
- May occur during any defrost.
- Heat signal has been on for too long.
- Time limit is 90 minutes with supply voltage above
440VAC and 120 minutes below 440VAC.
- Indicates:
- Low power supply voltage.
- Defective heater elements.
- Evaporator fans running during defrost.
- Evaporator sensor placed wrong.
Corrective Action
- Initiate a manual defrost and check amperage
draw and evaporator coil temperature.
Evaluate defrost performance.
- Open evaporator door and check location of
evaporator coil sensor.
NOTE: This alarm can be activated at low
voltage and very low box temperature
conditions, even under normal operating
conditions.