22 Capacity Test 1 Error MP4000
Description
Capacity Test 1 Error
- Occurs during pretrip (PTI) test only.
- Difference between supply and return air
temperature is too small with high speed
evaporator fans (less than approximately 4.5 C [8
F]).
- When the return air temperature does not reach
-18 C (0 F) within preset time.
- Indicates:
- Incorrect location of supply or return air sensor.
- Air leakage at supply sensor cable.
- Defective supply or return air sensor.
- Interchanged sensor connections.
- Incorrect evaporator fan rotation or high speed
operation.
- Incorrect refrigeration system operation.
- Container/side panels defective, damaged or
leaking.
- Economizer circuit defective.
Corrective Action
- Enter Manual Function Test and start
evaporator fans on high speed and let operate
fans for 5 minutes. Check supply, return and
evaporator coil (defrost) sensor temperatures.
Sensor readings should be the same
(evaporator coil may be 0.5 C [1.0 F] lower
due to fan motor heat).
- Open evaporator door and inspect evaporator
fan rotation. Make sure fans are rotating
correctly on high speed.
- Check the sensor connections.
- Enter Manual Function Test menu. Start and
check current draw of the following
components separately and together:
compressor, vapor on, condenser fan and
evaporator fans (high). Check discharge and
suction pressure readings. Also check the
refrigerant charge.
NOTE: This alarm can be activated in
ambient temperatures below -10 C (14 F),
even under normal conditions.