23 Capacity Test 2 Error (Check Alarm)

Thermo King Alarm Code
Description Corrective Action
Capacity Test 2 Error (Check Alarm)
  • Occurs during Pretrip (PTI) test only.
  • Difference between supply and return air temperature is too small with high speed evaporator fans (less than approximately 3.0 C (5.4 F); or temperature difference is less than in test P1.15. 
  • Return air temperature does not reach 0 C (32 F) within preset time.
  • Indicates:
  • Incorrect location of supply or return air sensor
  • Air leakage at supply, return or defrost (evaporator coil) sensor cable
  • Defective supply or return air sensor
  • Interchanged sensor connections
  • Incorrect evaporator fan rotation or low speed operation
  • Incorrect refrigeration system operation
  • Container/side panels defective, damaged or leaking
  • Enter Manual Function Test and start evaporator fans on HIGH speed. Then select Sensor Checks test and operate fans 2 to 5 minutes. Check supply, return and evaporator coil (defrost) sensor temperatures. Sensor readings should be the same (evaporator coil may be 0.5 C [1.0 F] lower due to fan motor heat).
NOTE: This sensor check does not detect air leakage around the sensor cables.
  • Open evaporator door and inspect evaporator fan rotation. Make sure fans are rotating correctly on high speed.
  • Check the sensor connections.
  • Enter Manual Function Test menu. Start and check current draw of the following components separately and together: compressor, compressor 100%, condenser fan and evaporator fans (high). Check the refrigerant charge using the “Unit Health Check Procedure” on page 6-5.
NOTE: Alarm can be activated in ambient temperatures
below -10 C (14 F), even under normal conditions.