23 Capacity Test 2 Error MP4000
Description
Capacity Test 2 Error
- Occurs during pretrip (PTI) test only.
- When the supply air temperature does not reach 0
°C (32 F) within preset time.
- Indicates:
- Incorrect location of supply air sensor.
- Air leakage at supply sensor cable.
- Defective supply air sensor.
- Interchanged sensor connections.
- Incorrect evaporator fan rotation or high speed
operation.
- Incorrect refrigeration system operation.
- Container/side panels defective, damaged or
leaking.
- Air exchange vent open too much.
- Low refrigerant charge.
- Cooling circuit defective.
Corrective Action
- Enter Manual Function Test and start
evaporator fans on high speed and let operate
fans for 5 minutes. Check supply, return and
evaporator coil (defrost) sensor temperatures.
Sensor readings should be the same (supply
air may be 0.5 °C [1.0 F] higher due to fan
motor heat).
- Open evaporator door and inspect evaporator
fan rotation. Make sure fans are rotating
correctly on low and high speed.
- Check the sensor connections.
- Enter Manual Function Test menu. Start and
check current draw of the following
components separately and together:
compressor, vapor on, condenser fan and
evaporator fans (high). Check discharge and
suction pressure readings. Also check the
refrigerant charge.