24 Capacity Test 3 Error (Check Alarm)

Thermo King Alarm Code
Description Corrective Action
Capacity Test 3 Error (Check Alarm)
  • Occurs during Pretrip (PTI) test only.
  • Difference between supply and return air temperature is too high with Stepper valve almost closed and high speed evaporator fans (more than 1.5 C [2.7 F]).
  • Indicates:
  • Defective Stepper valve
  • Incorrect location of supply or return air sensor
  • Defective supply or return air sensor
  • Expansion valve open too much
  • Incorrect refrigeration system operation
  • Container/side panels defective, damaged or leaking
  • Enter Manual Function Test and start the following components: Condenser fan, evaporator fan (high), compressor and compressor 25%. Check to be sure the Stepper valve closes.
  • Check the supply and return air sensor connections.
  • Check the supply and return air sensor calibration.
  • Check expansion valve superheat setting.