Capacity Test 3 Error (Check Alarm)
- Occurs during Pretrip (PTI) test only.
- Difference between supply and return air temperature is too high with Stepper valve almost closed and high speed evaporator fans (more than 1.5 C [2.7 F]).
- Indicates:
- Defective Stepper valve
- Incorrect location of supply or return air sensor
- Defective supply or return air sensor
- Expansion valve open too much
- Incorrect refrigeration system operation
- Container/side panels defective, damaged or leaking
|
- Enter Manual Function Test and start the following components: Condenser fan, evaporator fan (high), compressor and compressor 25%. Check to be sure the Stepper valve closes.
- Check the supply and return air sensor connections.
- Check the supply and return air sensor calibration.
- Check expansion valve superheat setting.
|