Heat Capacity Test Error (Check Alarm)
- Occurs during Pretrip (PTI) test only.
- Difference between supply and return air temperature too small with high speed evaporator fans (less than 0.4 C [0.7F]}.
- Indicates:
- Incorrect location of supply or return air sensor
- Air leakage at supply, return or evaporator coil sensor cable
- Defective supply or return air sensor
- Interchanged sensor connections
- Defective heater elements
- Incorrect evaporator fan rotation or high speed operation
- Container/side panels, defective, damaged or leaking
|
- Enter Manual Function Test and start evaporator fans on HIGH speed. Then select Sensor Checks test and operates fans 2 to 5 minutes. Check supply, return and evaporator coil (defrost) sensor temperatures. Sensor readings should be the same (evaporator coil may be 0.5 C [1.0 F] lower due to fan motor heat).
NOTE: this sensor check does not detect air leakage around the sensor cables
- Open evaporator door and inspect evaporator fan rotation. make sure fans are rotating correctly on high speed.
- Check the sensor connections.
|