Liquid Injection Valve Error (Pretrip) (Check Alarm)
- Occurs during Function or Pretrip (PTI) test only
- Indicates:
- Faulty bypass valve or circuit
|
- Energize and de-energize the bypass valve using “Injection Valve” in the COntroller Manual Function Test submenu. Confirm by sound that the valve energizes and de-energizes.
- If the valve does not operate, check the valve coil for continuity using a high quality multimeter.
- Check the circuit wiring in plug J11 for continuity using a high quality multimeter and a wiring diagram.
|