31 Low Pressure Cutout Error

Thermo King Alarm Code
Description Corrective Action
Low Pressure Cutout Error (Check Alarm)
  • Occurs any time.
  • Compressor does not stop during Function or Pretrip (PTI) test.
  • Indicates:
  • ~Stepper motor valve will not open
  • ~Bypass (warm gas) valve will not open (energize)
  • ~Low refrigerant charge
  • ~Defective low pressure cutout switch
  • Check the wiring to stepper motor valve using unit wiring diagrams and a digital multimeter. ~Disconnect stepper motor valve leads and check circuit resistance. Resistance should be 75 +/- 7.5 ohms at 24 C (75 F) between red/green and white/yellow wire leads. Be sure to maintain correct polarity or valve will not work.
  • Check bypass valve circuit wiring in plug J11 for continuity using a high quality multimeter.
  • If the bypass valve does not operate, check valve coil for continuity using a high quality multimeter.
  • Check the refrigerant charge using the “Unit Health Check Procedure” on page 6-5.
  • Continuity check low pressure cutout switch wiring using a high quality multimeter. Replace switch.