Cd51 Automatic Cold Treatment Parameter Selection

ACT-mode:
Cd51 increments of (1 day)_(1hr), Display: default “0_0 “
“done” mm-dd this will be display is ACT has completed
“ACt” value “On” “OFF” or “----“Display /Select: default “OFF“
“trEAt” value C / F on 0.1 degree increments Display/Select: default “0.0 C“
“DAyS” value “0 – 99” increments of 1 Display/Select: default “0“
“ProbE” value Probe positions ex ’1 2 _ 4’ ’1 _ 3 _’ Display: default “---- “
“SPnEW” value C / F on 0.1 increments Display/Select: default “10.0 C “
Initially Cd51 will display current countdown timer increments of (1 day)_(1hr), default
“0_0
Pressing ENTER key will take the interface down into a hierarchy of parameter
selection menus (act, treat, days, probe and spnew setting).
Pressing ENTER key in any of the parameter selection menus commits to selection
of the currently displayed parameter and causes the interface to descend into
the next parameter selection menu. All parameter selection menus alternate
between a blank display and the current selection in the right hand display.
Pressing CODE SELECT key in a selection menu cancels the current selection
activity and ascends back up to the next higher selection menu (or to Cd51 display
mode if that is the next higher).
If the operator does not press any key for five seconds the interface reverts to
normal system display and the current selection menu is cancelled, but any previously
committed changes are retained.
Available parameters and parameter ranges are a function of configuration options
and previously selected parameters as indicated above.
Parameter with the exception of “Act” may not be altered if Cd51 is re-entered if
“Act” is “On”. When ACT has completed including reaching the new setpoint
“done” on the left display and the MONTH DAY of completion on the right display
will be displayed as the second entry in the menu. Turning ACT off clears this
entry. This action also resets Cd51 to initial time remaining. ACT must then be
turned on to view or modify the additional parameters.
Whenever any auto Pre-trip test or Trip Start is initiated, ACT mode goes to OFF.