37 Total Current Too Low (Log Alarm)

Thermo King Alarm Code
Description Corrective Action
Total Current Too Low (Log Alarm)
  • Compressor Start-up: Unit or component current draw is 50% below expected amps for 4 minutes.
  • Indicates:
  • Defective or open fuse CB 7A
  • Defective or open high pressure cutout switch
  • Defective evaporator high temperature protection switch
  •  Defective or open motor internal high temperature protection switch
  • Unit on water-cooled condensing with no water flow
  • Defective condenser coil sensor or sensor location
  • Check LCD display for High Pressure Cutout message.
  • Enter Manual Function Test menu and test (operate) each component. Check volts and amps to determine which component has low amp draw.
  • Check volt and ampere meter.