Total Current Too Low (Log Alarm)
- Compressor Start-up: Unit or component current draw is 50% below expected amps for 4 minutes.
- Indicates:
- Defective or open fuse CB 7A
- Defective or open high pressure cutout switch
- Defective evaporator high temperature protection switch
- Defective or open motor internal high temperature protection switch
- Unit on water-cooled condensing with no water flow
- Defective condenser coil sensor or sensor location
|
- Check LCD display for High Pressure Cutout message.
- Enter Manual Function Test menu and test (operate) each component. Check volts and amps to determine which component has low amp draw.
- Check volt and ampere meter.
|