415 StarCool Alarm Codes And Actions

415  Over voltage
Description U1-2 and U1-3 and U2-3 over voltage
Cause Indication of error in container supply voltage between phases
Trouble
shooting
Possible causes:

  • The unit is supplied with a voltage above specified level.

Trouble shooting:

  1. Try to correct the error by uploading the latest software version to the controller.
  2. Measure the voltage applied to the unit.
  3. Apply correct voltage to the unit.
  4. The FC will be destroyed if it is running at a too high voltage.
  5. Measure the actual voltage and compare with the value in the display. If the measurement differs the power module PCB may be defective. Replace or bypass power module PCB by pressing (spaner icon) selecting configuration then phase direction and then cw. If condenser fan rotates in the wrong direction, choose ccw. This action is to be performed at every unit start up
Criteria Value above top alarm limit 525 Volt