Evaporator Coil Temperature Too Low codes. (Check Alarm)
- During Chill or Frozen Mode: Evaporator coil temperature is too low compared to return air temperature under actual operating conditions.
- Controller initiates defrost if no recent defrost.
- Indicates:
- Airflow is blocked in the container
- Evaporator fans do not operate
- Fresh air exchange vent open too much on frozen load
- Defective evaporator coil or return air sensor
|
- Check for sensor or evaporator fan alar
- Open evaporator door. Inspect coil for ice or frost and initiate manual defrost if necessary. Check for correct evaporator fan rotation and operation.
- Inspect return air grille and cargo load. Remove any debris or cargo from blocking return air grille.
- At setpoints below 5 C (41 F), maximum air vent setting is not allowed.
- Check evaporator coil and return air sensor connections and locations.
|