513 | Compr overload |
---|---|
Description | Compressor Overload Alarm |
Cause | Indication of problems with compressor |
Trouble shooting |
Possible causes:
Trouble shooting: At very high ambient temperatures and very low setpoint temperatures, the FC may get too hot to generate enough power. Therefore it can be cooled by the refrigerant in the compressor.
V-Y 1.15 Ω U-X 1.15 Ω W-Z 1.15 Ω Also ensure to check to ground Meggering: Value above 5 MΩ = OK Value below 5 MΩ = Remove terminal block and measure again, directly: the compressor
6. The compressor is wearing down and drawing increasingly power from the FC. |
Criteria | Compressor overloaded. Current has been above 24 Amp for 20 sec. |
513 StarCool Alarm Codes And Actions