53 High Pressure Cutout Switch Off Error

Thermo King Alarm Code
Description Corrective Action
High Pressure Cutout Switch Off Error (Check Alarm)
  • Occurs during Pretrip (PTI) test only.
  • Compressor does not stop during high pressure cutout switch test.
  • Indicates:
  • Faulty compressor contactor or control circuit
  • Low refrigerant charge
  • Defective high pressure cutout switch
  • Strong winds causing cooling of condenser coil in low ambient conditions
  • Check discharge and suction pressure gauge readings and check refrigerant charge.
  • Enter Manual Function Test menu. Start the following components together: compressor 100%, compressor and evaporator fans (high). Discharge pressure should increase and compressor should stop at 2250 kPa, 22.5 bar, 326 psig (high pressure cutout switch opens).