53 High Pressure Switch Off Error MP4000
Description
High Pressure Switch Off Error
- Occurs during pretrip (PTI) test only.
- Compressor does not stop during high pressure
cutout switch test.
- Indicates:
- Faulty compressor contactor or control circuit.
- Low refrigerant charge.
- Defective high pressure cutout switch.
- Strong winds causing cooling of condenser coil in
low ambient conditions.
Corrective Action
- Check discharge and suction pressure gauge
readings and check refrigerant charge.
- Enter Manual Function Test menu.
- Start the following components together:
compressor 100 percent, compressor and
evaporator fans (high). Discharge pressure
should increase and compressor should
stop at 2250 kPa, 22.5 bar, 326 psig (high
pressure cutout switch opens).