54 High Pressure Switch On Error MP4000
Description
High Pressure Switch On Error
- Occurs during pretrip (PTI) test only.
- Compressor does not start within normal time
during high pressure cutout switch test.
- Indicates:
- High pressure cutout switch did not respond to
pressure change within 5 seconds.
- Air in refrigeration system.
- Defective high pressure cutout switch.
Corrective Action
- Check discharge and suction pressure gauge
readings.
- Enter Manual Function Test menu.
- Start the following components together:
compressor 100 percent, compressor and
evaporator fans (high). Discharge pressure
should increase and compressor should
stop at 2250 kPa, 22.5 bar, 326 psig (high
pressure cutout switch opens).
- Then start condenser fan. Discharge
pressure must drop quickly (10 to 20
seconds) to 1550 kPa, 15.5 bar, 225 psig
and compressor should start (switch
closes).