56 Compressor Temperature Too High MP4000
Description
Compressor Temperature Too High
- Shutdown Alarm
- Compressor discharge line temperature is above
148 C (298 F). Compressor stopped until discharge
line temperature decreases to normal.
- Indicates:
- Air in refrigeration system.
- Low refrigerant charge.
- Defective compressor.
- Defective vapor injection.
Corrective Action
- Operate unit on Cool and check discharge and
suction pressure gauge readings.
- Enter Manual Function Test menu and test
(operate) Vapor Injection Valve to determine if
valve opens (energizes).
- Check compressor discharge sensor
resistance. Resistance must be approx.
86,000 ohms at 25 C (77 F).
- Check discharge line temperature with a
separate electronic thermometer and compare
to “HIGH PR TEMP” shown in the Data menu
of controller.
NOTE: Unit will operate normally without
compressor sensor. However, controller
compressor high temperature protection is
not active.