56 Compressor Temperature Too High MP4000

Description 

Compressor Temperature Too High 

  • Shutdown Alarm 
  • Compressor discharge line temperature is above 148 C (298 F). Compressor stopped until discharge line temperature decreases to normal. 
  • Indicates: 
  • Air in refrigeration system. 
  • Low refrigerant charge. 
  • Defective compressor. 
  • Defective vapor injection. 

Corrective Action 

  • Operate unit on Cool and check discharge and suction pressure gauge readings. 
  • Enter Manual Function Test menu and test (operate) Vapor Injection Valve to determine if valve opens (energizes). 
  • Check compressor discharge sensor resistance. Resistance must be approx. 86,000 ohms at 25 C (77 F). 
  • Check discharge line temperature with a separate electronic thermometer and compare to “HIGH PR TEMP” shown in the Data menu of controller. 
NOTE: Unit will operate normally without compressor sensor. However, controller compressor high temperature protection is not active.