Compressor Temperature Too High (Shutdown Alarm)
- Compressor discharge temperature is above 148 C (298 F). Compressor stopped until discharge temperature decreases to normal;
- Indicates:
- Air in refrigeration system
- Low refrigerant charge
- Defective compressor or valve plate
- Defective liquid injection system
- Wrong or defective sensor
|
- Check the refrigerant charge using the “Unit Health Check Procedure” on page 6-5.
- Enter Manual Function Test menu and test (operate) Injection Valve to determine if valve opens (energizes).
- Check compressor discharge sensor resistance. Resistance must be 100,000 ohms at 25 C (77 F).
- Check discharge temperature with a separate electronic thermometer and compare to “HIGH PR TEMP” shown in the Data menu of controller.
NOTE: Unit will operate normally without compressor sensor. However, controller compressor high temperature protection is not active. |