57 FAE Device Error MP4000

Description 

FAE Device Error 

  • Occurs during pretrip testing if the expected door endpoints can’t be reached. 
  • Occurs during normal operation 
  • If the AFAM+ module isn’t detected. 
  • During door position calibration the expected door endpoints feedback can’t be reached. 
  • During pulsing movement the expected door end points feedback can’t be reached. 
  • Indicates: 
  • Stocked air vent. door motor. 
  • Failing or missing AFAM+ module. 

Corrective Action 

  • Inspect AFAM+ module connection to the controller. 
  • Using STATES MENU / EXPANSION MODULE to inspect the observed presence and readings of the AFAM+ module. 
    • From backside left bay is bay 1 
    • From backside right bay is bay 2 
      • If the module is not found use the tester to decide the problem. 
  • Inspect wiring from AFAM+ motor to AFAM+ module. 
  • Using MANUAL FUNCTION TEST move and Inspect air vent door movement. 
  • Inspect air vent. 
  • Replace AFAM+ motor.