Trouble
shooting |
Possible causes:
- There has been too much ice in the evaporator.
- The heaters are not working/defective.
- Defective Psuc pressure transmitter.
- Defective Pdis pressure transmitter.
- Defective Tevap evaporator temperature sensor.
- Lack of refrigerant
Accompanied alarms
- Maybe alarm AL 203 is active.
Trouble shooting:
- Check and clear other alarms first. Check refrigerant level.
- Check pressure transmitter configuration and confirm values from Psuc and Pdis by comparing them to gauge readings.
- Start a manual defrost time to remove remaining ice now. See if there has been used current for the heaters on the information menu - Current phase 1, 2 and 3 should be above 6 A when the heater symbol, , is shown on the display. If current is lower, check if there is power for the heaters.
- Run a PTI test after the cargo is unloaded.
|