Trouble
shooting |
Possible causes:
- Defective power supply for main controller.
- Defective Psuc pressure transmitter.
- Defective main controller.
Accompanied alarms:
- There may be sensor alarms, especially AL 207.
- AL 801 will be activated during FT- or PTI test.
Trouble shooting:
- Check if there are other active (sensor) alarms. Clear these alarms fi rst using their trouble shooting.
- Access the “special menu” by pressing "spanner icon" for more than 3 sec. Scroll down until you see the label “U Psuc” in the display. The value of “U Psuc“ should be in the range between 4.80 and 5.2V DC.
- While displaying “U Psuc“, remove the connector at Psuc. − If “U Psuc” is now inside the correct above range (4.80 – 5.2 V DC), the Psuc pressure transmitter is defective. Replace the Psuc pressure transmitter. − If “U Psuc” is still outside the above range, proceed to next step.
- While displaying “U Psuc“, disconnect Pdis from the terminals according to wiring schematics inside in the control cabinet. − If “U Psuc” is now inside the above range the cable for Psuc is defective. Mount connector correctly or replace connector cable for Psuc. − If the correct voltage is measured at X22 then circuit is defective.
Replace the main controller. |