Compressor Sensor Open Circuit (Check Alarm)
- Sensor circuit resistance higher than 100,000 ohms.
- Temperature below -30 C (-22 F).
- Indicates:
- Open circuit to sensor
- Defective or wrong sensor
- Defective relay board
- Defective cable No.1
- Defective controller
|
- Check sensor resistance between pins 9 and 10 on plug J15. Resistance must be 100,000 ohms at 25 C (77 F).
- Check cable No. 1 between controller and relay board.
NOTE: Unit will operate normally without compressor sensor. However, controller compressor high temperature protection is not active.
|