AL14 Phase Sequence Detect Fault

Cause
  • Controller is unable to determine the correct phase relationship.
Components Troubleshooting Corrective actions
N/A Power cycle the unit. Resetting the unit may correct problem, monitor the unit.
Wiring Check unit wiring. Confirm pressure readings during start-up; suction pressure should decrease and discharge pressure should increase. Correct wiring.
Current Sensor Check Cd41, right most digit: If display is 3 or 4 check compressor / sensor wiring. If display is 5 the current sensor is defective. Replace current sensor if defective.