Cause
- Controller is unable to determine the correct phase relationship.
Components | Troubleshooting | Corrective actions |
---|---|---|
N/A | Power cycle the unit. | Resetting the unit may correct problem, monitor the unit. |
Wiring | Check unit wiring. Confirm pressure readings during start-up; suction pressure should decrease and discharge pressure should increase. | Correct wiring. |
Current Sensor | Check Cd41, right most digit: If display is 3 or 4 check compressor / sensor wiring. If display is 5 the current sensor is defective. | Replace current sensor if defective. |