AL19 Discharge Temperature High

Cause
  • Discharge temperature exceeds 135 C (275 F) for 10 minutes within the last hour.
Components Troubleshooting Corrective actions
Restrictions in the
refrigeration
system.
Ensure the Discharge Service Valve is fully open. Open the Discharge Service Valve as needed.

Check the unit for air flow restrictions. Clean or remove any debris from coils.
Non-condensables in the refrigeration system. With the unit off allow system to stabilize to ambient temperature. Check system pressure against PT Chart for 134a, refer to Table 6−4. Correct as required, refer to Refrigerant Charge Section 6.7.1.
Additional Alarms such as AL16, AL24. Check compressor operation. If the alarm persists, it may indicate a failing compressor, replace the compressor, refer to COMPRESSOR Service Section 6.8.