AL20 Control Contactor Fuse (F3)

Cause
  • Control power fuse (F3A or F3B) is open.
Components Troubleshooting Corrective actions
Check F3A, if the fuse is open: Check PA, PB, CH coils for short to ground, if short is found: Replace the defective coil. Replace the fuse.
Check F3B, if the fuse is open: Check ESV coil resistance at TP7 to TP9, if short to ground, or if resistance is less than 4 ohms, coil is defective. Check CF, ES, EF, HR coils for short to ground, if short is found, coil is defective. Replace the defective coil. Replace the fuse.
Check Voltage at QC1: If voltage is present, it indicates a defective microprocessor. Refer to Controller Service Section 6.23.